Technical data

Technical data with refrigerant R-407C (DX-radiator)
WUC = upward blowing with liquid chilling
WDC = downward blowing with liquid chilling
Nominal condensing output at room temperature 24º C, 50 %, condensation temperature 45º C
Dual-circuit units
Device type 130-2 140-2
Total output kW 50 58
Sensible output kW 46 49
Condensing output requirement kW 65 75
Compressors (hermetic) 400V-3ph-50Hz
Number 2 2
Power requirement kW 15 18
Centrifugal fans 230V-1Ph-50Hz direct-drive
Number 3 3
Air quantity m3/s 3,18 3,18
External pressure Pa 60 60
Motor output kW 2,25 2,25
Filters EU5
Number 3 3
Size: upward blowing 600x600 600x600
Size: downward blowing 560x650 560x650
After-heating 400V-3Ph-50Hz
Heating output kW 12 12
Number of elements 4 4
Number of steps 3 3
Humidification 400V-3Ph-50Hz
Humidification output kg 9,4 9,4
Connected load kW 6,9 6,9
Dimensions and weight
Width mm 2300 2300
Depth mm 650 650
Height mm 1920 1920
Weight kg 490 490
Exhaust chamber height 500 mm
(to be added to height of unit, model WUC)
Connections
Humidifier mm 6 6
Drain mm 32 32
Unit´s electrical connected load 400V-3Ph-50Hz
Types A and E kW 17,5 21,0
Type B kW 29,3 33,0
Type C kW 24,2 27,9
Type D kW 36,2 39,9
Liquid chiller selections
WUC- and WDC units
Device type 130-2 140-2
Condensing output requirement kW 65 75
Liquid chillers (outdoor temperature 30°C, liquid temperature 37 / 42°C (nominal value), 35 % propylene glycol)
Alternative 1 CCSG 15-9-50-22 CCSG 16-11-65-25
Noise level dB(A) at 10-m distance 49 51
Liquid flow l/s 3,0 3,4
Pressure drop kPa 32,5 30,9
Alternative 2 CCSG 14-11-65-23 CCSG 14-14-65-26
Noise level dB(A) at 10-m distance 54 51
Liquid flow l/s 3,1 3,5
Pressure drop kPa 34,1 27,6
Siirry sivun alkuun