Technical data

Technical data with refrigerant R-407C (DX-radiator)
WUC = upward blowing with liquid chilling
WDC = downward blowing with liquid chilling
Nominal condensing output at room temperature 24º C, 50 %, condensation temperature 45º C
Dual-circuit units
Device type 075-2 090-2 110-2
Total output kW 30 37 45
Sensible output kW 29 33 37
Condensing output requirement kW 39 48 59
Compressors (hermetic) 400V-3ph-50Hz
Number 2 2 2
Power requirement kW 9 11,1 13,5
Centrifugal fans 230V-1Ph-50Hz direct-drive
Number 2 2 2
Air quantity m3/s 2,3 2,3 2,3
External pressure Pa 60 60 60
Motor output kW 0,75 1,5 1,5
Filters EU5
Number 2 2 2
Size: upward blowing 600x600 600x600 600x600
Size: downward blowing 560x650 560x650 560x650
After-heating 400V-3Ph-50Hz
Heating output kW 5 6,6 12
Number of elements 2 2 2
Number of steps 2 2 3
Humidification 400V-3Ph-50Hz
Humidification output kg 4,7 4,7 9,4
Connected load kW 3,4 3,4 6,9
Dimensions and weight
Width mm 1775 1775 1775
Depth mm 650 650 650
Height mm 1920 1920 1920
Weight kg 280 465 475
Exhaust chamber height 500 mm
(to be added to height of unit, model WUC)
Connections
Humidifier mm 6 6 6
Drain mm 32 32 32
Unit´s electrical connected load 400V-3Ph-50Hz
Types A and E kW 11,3 12,6 15,0
Type B kW 16,3 19,2 27,0
Type C kW 14,7 17,3 21,9
Type D kW 19,7 23,9 33,9
Liquid chiller selections
WUC- and WDC units
Device type 075-2 090-2 110-2
Condensing output requirement kW 39 48 59
Liquid chillers (outdoor temperature 30°C, liquid temperature 37 / 42°C (nominal value), 35 % propylene glycol)
Alternative 1 CCSG 10-11-50-18 CCSG 15-7-50-16 CCSG 14-9-50-21
Noise level dB(A) at 10-m distance 41 41 49
Liquid flow l/s 2,5 2,1 2,9
Pressure drop kPa 29,0 39,1 35,6
Alternative 2 CCSG 9-14-50-15 CCSG 10-14-50-19 CCSG 13-11-50-21
Noise level dB(A) at 10-m distance 58 56 54
Liquid flow l/s 2,1 2,6 2,9
Pressure drop kPa 30,3 29,2 34,5
Siirry sivun alkuun