Technical data

Technical data with refrigerant R-407C (DX-radiator)
AUC = upward blowing direct condensation
ADC = downward blowing direct condensation
Nominal chilling output at room temperature 24º C, 50 %, condensation temperature 45º C
Dual-circuit units
Device type 130-2 140-2
Total output kW 50 58
Sensible output kW 46 49
Chilling output requirement kW 65 75
Compressors (hermetic) 400V-3ph-50Hz
Number 2 2
Power requirement kW 15 18
Centrifugal fans 230V-1Ph-50Hz direct drive
Number 3 3
Air quantity m3/s 3,18 3,18
External pressure Pa 60 60
Motor output kW 2,25 2,25
Filters EU5
Number 3 3
Size: upward blowing 600x600 600x600
Size: downward blowing 560x650 560x650
After-heating 400V-3Ph-50Hz
Heating output kW 12 12
Number of elements 4 4
Number of steps 3 3
Humidification 400V-3Ph-50Hz
Humidification output kg 9,4 9,4
Connected load kW 6,9 6,9
Dimensions and weight
Width mm 2300 2300
Depth mm 650 650
Height mm 1920 1920
Weight kg 490 490
Exhaust chamber height 500 mm
(to be added to height of unit, models AUC, WUC)
Connections
Humidifier mm 6 6
Drain mm 32 32
Unit´s electrical connected load 400V-3Ph-50Hz
Types A and E kW 17,5 21,0
Type B kW 29,3 33,0
Type C kW 24,2 27,9
Type D kW 36,2 39,9
Condenser selections
AUC and ADC units
Device type 130-2 140-2
Condensing output requirement kW 65 75
Condensers (outdoor temperature 30°C, condensation temperature 45°C)
Alternative 1 CCS 13-9 CCS 14-9
Noise level dB(A) at 10-m distance 48 49
Alternative 2 CCS 11-14 CCS 12-14
Noise level dB(A) at 10-m distance 60 58