Technical data

Technical data with refrigerant R-407C (DX-radiator)
AUC = upward blowing direct condensation
ADC = downward blowing direct condensation
Nominal chilling output at room temperature 24º C, 50 %,
condensation temperature 45º C
Dual-circuit units
Device type 050-2 060-2
Total output kW 22 24
Sensible output kW 18 20
Chilling output requirement kW 29 31
Compressors (hermetic) 400V-3ph-50Hz
Number 2 2
Power requirement kW 6,6 8,5
Centrifugal fans 230V-1Ph-50Hz direct drive
Number 1 1
Air quantity m3/s 1,06 1,25
External pressure Pa 60 60
Motor output kW 0,75 0,75
Filters EU5
Number 1 1
Size: upward blowing 560x600 560x600
Size: downward blowing 560x650 560x650
After-heating 400V-3Ph-50Hz
Heating output kW 5 5
Number of elements 2 2
Number of steps 2 2
Humidification 400V-3Ph-50Hz
Humidification output kg 4,7 4,7
Connected load kW 3,4 3,4
Dimensions and weight
Width mm 1010 1010
Depth mm 650 650
Height mm 1920 1920
Weight kg 260 270
Exhaust chamber height 500 mm
(to be added to height of unit, models AUC, WUC)
Connections
Humidifier mm 6 6
Drain mm 32 32
Unit´s electrical connected load 400V-3Ph-50Hz
Types A and E kW 7,4 9,3
Type B kW 12,4 14,3
Type C kW 10,8 12,7
Type D kW 15,8 17,7
Condenser selections
AUC- and ADC units
Device type 050-2 060-2
Condensing output requirement kW 29 31
Condensers (outdoor temperature 30°C, condensation temperature 45°C)
Alternative 1 CCS 8-9 CCS 8-11
Noise level dB(A) at 10-m distance 45 48
Alternative 2 CCS 6-14 CCS 7-14
Noise level dB(A) at 10-m distance 55 54
Siirry sivun alkuun